Water treatment plant for continuous pickling line
Industry
Application
Water treatment plant
Task
The plant is designed for the demineralized
water needs of the continuous pickling line
Water source
Factory network
About the project
Basic and detailed engineering, equipment manufacturing, supervision
of erection, and commissioning were performed during the project
implementation. The water treatment system is designed to operate in
automatic mode.
The temperature parameter is one of the key parameters in the membrane
technology process. It has an impact on the demineralized water quality
and performance of water treatment equipment. Since the temperature
of the feed water coming into the demineralization plant was too high for
ultrafiltration and reverse osmosis membranes, it was cooled.
Technologies
Heat exchange -> Active carbon -> Ultrafiltration -> Reverse Osmosis
Fact and figures
Quality indicators, units of measurement | Feed water | Demineralized
water |
Value | Value | |
Flowrate, m3/h | < 35 | Average 5,5
Max 35 |
рН | 8.6 – 9.3 | 7.0 – 8.5 |
Electrical conductivity, μS/cm | 170 – 335 | < 20 |
Total hardness, mg/l СаСО3 | 50 – 100 | < 0.5 |
Alkalinity, mg/l СаСО3 | 79 – 123 | < 2.0 |
Chlorides, mg/l | 2 – 16 | < 0.5 |
Sulphates, mg/l | < 30 | < 0.5 |
Suspended matters, mg/l | 0 – 2,2 | 0 – 0.5 |
Salinity, mg/l | 120 – 240 | < 10 |
Oil products, mg/l | 0.07 – 0.36 | |
Temperature, °С | 75 | 20-30 |
Summarize
There were used advanced technologies for the demineralization process in this project. Solutions, made
in this project, allow our customer to minimize chemical reagent consumption in comparison to traditional
technologies. Turbidity, suspended solids, iron, organic compounds, and salinity were reduced during the
water treatment process.